Title 13 PUBLIC SERVICES
Chapter 13.72 BACKFLOW AND CROSS-CONNECTIONS
13.72.370 Protection against backflow and siphonage.
A. Water Outlets. A potable water system shall be protected
against backflow and back-siphonage by providing and maintaining at each
outlet:
1. Air Gap. An air gap, as specified in subsection B of this
section, between the potable water outlet and the flood-level rim of the fixture
it supplies or between the outlet and any other source of contamination;
or
2. Backflow Preventer. An approved device or means to prevent
backflow.
B. Minimum Required Air Gap.
1. How Measured. The minimum required air gap shall be
measured vertically from the lowest end of a potable water outlet to the flood
rim or line of the fixture or receptacle into which it discharges.
2. Size. The minimum required air gap shall be twice the
effective opening of the potable water outlet unless the outlet is a distance
less than three times the effective opening away from a wall or similar vertical
surface, in which cases the minimum required air gap shall be three times the
effective opening of the outlet. In no case shall the minimum required air gap
be less than shown in Table 13.72.370(1), codified at the end of this
chapter.
C. Approval of Devices. 1. Before any device for the
prevention of backflow or siphonage is installed, it shall have first been
certified by a recognized testing laboratory acceptable to the agency director.
Devices installed in a building’s potable water supply distribution system
for protection against backflow shall be maintained in good working condition by
the person or persons responsible for the maintenance of the system.
2. The agency director or his designee shall inspect
routinely such devices and if they are found to be defective or inoperative,
shall require the replacement thereof.
D. Installation of Devices.
1. Nonpressure Type Vacuum Breakers. Atmospheric vacuum
breakers shall be installed with the critical level at least six inches above
the flood-level rim of the fixture they serve, and on the discharge side of the
last control valve to the fixture. No shutoff valve or faucet shall be installed
beyond the vacuum breaker. For closed equipment or vessels such as pressure
sterilizers the top of the vessel shall be treated as the flood-level rim but a
check valve shall be installed on the discharge side of the vacuum
breaker.
2. Reduced Pressure Principle Backflow Preventer. A reduced
pressure principle backflow preventer may be installed subject to full static
pressure.
3. Devices of All Types. Backflow and back-siphonage
preventing devices shall be accessibly located, preferably in the same room with
the fixture they serve. Installation in utility or service spaces, provided they
are readily accessible, is also permitted.
E. Tanks and Vats--Below Rim Supply.
1. Where a potable water outlet terminates below the rim of a
tank or vat and the tank or vat has an overflow of a diameter not less than that
given in Table 13.12.070(2), codified at the end of this chapter, the overflow
pipe shall be provided with an air gap as close to the tank as
possible.
2. The potable water outlet to the tank or vat shall
terminate a distance of not less than one and one-half times the height to which
water can rise in the tank above the top of the overflow. This level shall be
established at the maximum flow rate of the supply to the tank or vat with all
outlets except the air gap overflow outlet closed. The distance from the outlet
to the high water level shall be measured from the critical point of the potable
water supply outlet. The following diagram illustrates this principle:

Figure 3.85 Properly protected tank with below rim
supply.
F. Protective Devices Required. Approved devices to protect
against backflow and back-siphonage shall be installed at all fixtures and
equipment where backflow and/or back-siphonage may occur and where minimum air
gap cannot be provided between the water outlet to the fixture or equipment and
its flood level rim.
1. Connections Not Subject to Back Pressure. Where a water
connection is not subject to back pressure, a vacuum breaker shall be installed
on the discharge side of the last valve on the line serving the fixture or
equipment. A list of some conditions requiring protective devices of this kind
is given in Table 13.12.070(3), codified at the end of this chapter.
2. Connections Subject to Backpressure. Where a potable water
connection is made to a line, fixture, tank, vat, pump or other equipment with a
hazard of backflow or back-siphonage where the water connection is subject to
back pressure, and an air gap cannot be installed, the public works
administrator will require adequate protection which may include the use of an
approved reduced pressure principle backflow preventer. A partial list of such
connections is shown in Table 13.12.070(4).
G. Low Pressure Cutoff Required on Booster Pumps. When a
booster pump is required on a water pressure booster system and the possibility
exists that a positive pressure of less than 20 psi may occur on the suction
side of the pump, there shall be installed a low pressure cutoff on the booster
pump to prevent the creation of a vacuum or negative pressure on the suction
side of the pump, thus cutting off water to other outlets. (Ord. 1987-9 §
3.8, 1987)